AS4775-2007 Section 6.2 specifies exact dimensional requirements to ensure full-body coverage. These are mandatory - an installation outside these tolerances is non-compliant even if the unit itself is AS4775-certified.

Requirement Specification
Shower head height (bottom of head) Minimum 2,083mm — Maximum 2,438mm above standing surface
Spray pattern diameter Minimum 508mm at 1,524mm above standing surface
Centre of spray pattern clearance Minimum 406mm from any obstruction
Eyewash nozzle height 838mm minimum — 1,143mm maximum from standing surface
Eyewash nozzle wall clearance Minimum 153mm from any wall or obstruction

 

These dimensions ensure that a worker of average height stands fully within the spray pattern and receives adequate coverage across the shoulders and upper body during a flush.